Adloun

Physics (Grade 12 General Sciences, Lebanon) · Chapter 7 · Tutorial exercise

Hydroelectric power plant, step-up and step-down transformers and high-voltage energy transmission

Sinusoidal alternating current, RLC circuit and transformer · B. Series circuit, current resonance, transformer and energy transmission · level 3 (hard)

Statement

A hydroelectric power plant (comparable to the Markaba plant on the Litani) produces an average (active) electric power () at a sinusoidal alternating voltage of rms value and frequency with a power factor (voltage and current in phase). This energy must be transmitted to a city located away through a two-wire line of aluminum cable with a resistance per unit length per wire.

Part A — Impossibility of direct transmission at medium voltage ()

  1. Calculate the total length of conductor of the two-wire line and deduce the total resistance of the transmission line.
  2. If the power were injected directly into the line at the output voltage of the alternator (): a) What would be the rms current in the line? b) Calculate the ohmic voltage drop along the line and the power that would be dissipated by the Joule effect. Why is such direct transmission technically and economically impossible?

Part B — High-Voltage transmission () by means of a step-up transformer At the output of the plant, a step-up transformer , assumed ideal, is placed; it raises the voltage from to the high voltage at the input of the transmission line.

  1. Calculate the transformation ratio of transformer . By what factor is the rms line current divided compared with ? Calculate the numerical value of .
  2. Show that the power lost by the Joule effect in the line is written and calculate numerically (in ), as well as the percentage of power lost in the line and the efficiency of the transmission. By what factor have the Joule losses been divided by raising the voltage from to ?

Part C — Step-down substation at the arrival point and power factor correction

  1. Calculate the rms voltage available at the end of the HV line at the entrance to the city. An ideal step-down transformer brings this voltage down to a medium distribution voltage . Calculate the transformation ratio of and the rms current delivered at the secondary of .
  2. If the overall power factor of the city dropped from to (for the same active power transmitted at ), what would become of the line current and the power lost by the Joule effect ? Conclude on the advantage of compensating the inductance of the installations with capacitor banks.

Solution

Part A — Impossibility of direct transmission at

  1. Total resistance of the two-wire line. The line has two conductors (outgoing and return) of length each, that is, a total cable length :
  1. Current and losses in direct transmission at . a) From with : b) The ohmic voltage drop would represent of the initial voltage , and the power dissipated by the Joule effect would be: Thus, of the power produced by the plant would be lost as heat in the cables before even reaching the city: direct transmission at medium voltage is totally impracticable.

Part B — High-Voltage transmission () with the step-up transformer

  1. Transformation ratio and new line current . The transformation ratio of the step-up transformer is: Since transformer is ideal (), raising the voltage by a factor divides the line current by :
  1. Formula for the line losses and efficiency of HV transmission. From , we obtain: Numerical application (): The relative fraction of power lost in the line is now only: By multiplying the transmission voltage by , the Joule losses have been divided by ().

Part C — Step-down substation at the arrival point and influence of the power factor

  1. Voltage at the arrival point and step-down transformer . The voltage drop in the line is , hence the voltage at the input of the step-down substation : To obtain at the secondary of , the transformation ratio of must be: And the rms current delivered to the distribution grid of the city is:
  1. Effect of a deterioration of the power factor (). If , to transmit the same active power at , the line current increases: and the Joule losses are divided by (that is, multiplied by , i.e. additional losses): Keeping a power factor close to (resonance, by compensating the inductive character of motors with capacitors) minimizes both the line current and the Joule losses.

What the exercise establishes: Bring together the whole energy chain of the chapter: prove the law , justify quantitatively the joint use of a step-up transformer at the output of the plant and of step-down transformers at the arrival point, and relate the line losses to the power factor .