Physics (Grade 11 Humanities, Lebanon) · Chapter 3 · Direct application of the course
Choosing the rating of a fuse
Domestic electricity and its dangers · level 2
Statement
In a laundry room, the same line supplies at a washing machine and an iron. Fuses with ratings of , and are available.
- Calculate the total current when the two appliances run at the same time.
- What happens if the line is protected by the fuse?
- Which rating should be chosen?
- Why should the fuse not be chosen “to be on the safe side”?
Solution
- The total power is , so .
- exceeds : the fuse blows and cuts off the current every time the two appliances run together.
- The fuse: it is the smallest rating above the normal current of .
- The wires of the line are designed for a limited current. In the event of an overload, a fuse would let through a current far greater than these wires can withstand: they would heat up without the fuse blowing, with a risk of fire.