Too many appliances on a power strip

Domestic electricity and its dangers · B. Installation, dangers and protection · level 2

Statement

A power strip is plugged into a socket protected by a circuit breaker rated . A space heater and an iron are plugged into it.

1) How are these two appliances connected with respect to each other: in series or in parallel?

2) Calculate the total power, then the current in the cord of the power strip.

3) Does the circuit breaker cut off the current?

4) A kettle is plugged in as well. Calculate the new current. What happens?

5) What is this situation called? What danger has the circuit breaker prevented?

Solution

1) They are connected in parallel: each receives .

2) The powers add up:

3) No: is below the rating of .

4) The total power becomes : This current exceeds : the circuit breaker opens and cuts off the current.

5) It is an overload. Without a circuit breaker, the wires and the power strip would have heated up until their sheath melted: the circuit breaker has prevented a risk of fire.

Key takeaway: in parallel, the currents add up; the circuit breaker cuts off as soon as their sum exceeds its rating.