Physics (Grade 11, Lebanon) · Chapter 15 · Direct application of the course
Analyzing an insulation fault and the role of the ground and of the residual current device
Alternating current, transformer and household safety · level 3 (hard)
Statement
An electric oven of power has a metal casing. Following the wear of an internal insulator, the phase wire () accidentally comes into contact with the metal casing of the oven. A person with wet feet on the tiled floor (electrical resistance of their body ) puts a hand on the casing of the oven.
- Non-compliant installation (two-terminal socket with no ground wire and no residual current device, protected only by a fuse):
- To what electric potential is the metal casing of the oven raised?
- Calculate the current flowing through the person's body when they touch the oven. What are the physiological effects?
- Does the fuse blow and save this person? Justify by calculation.
- Compliant installation (casing connected to a ground of resistance and distribution board fitted with a residual current device of sensitivity ): explain what happens as soon as the insulation fault appears and why the person is protected.
Solution
- Installation with no ground and no residual current device:
- With no ground connection, the internal contact with the phase wire raises the whole metal casing of the oven to the potential of the phase, that is, relative to the ground.
- When the person touches the casing, they are subjected to the voltage between their hand and their feet on the ground (). By Ohm's law, their body carries a current of effective value:
This current () far exceeds the tetanization threshold () and the fatal threshold of cardiac fibrillation (): the person suffers fatal electrocution.
- In normal operation the oven draws . During the electrocution, the total current through the phase fuse is : the fuse does not blow at all! A fuse protects only against overcurrents (fires) and never against the electrocution of a person.
- Compliant installation (ground connection + residual current device): As soon as the phase wire touches the casing connected to the ground (), a leakage current flows directly to the ground through the green-yellow ground wire. Since this leakage current () immediately exceeds the threshold of difference between the phase current and the neutral current, the residual current device trips within a few milliseconds and cuts off the power supply, even before a user touches the oven.
Similar exercises
- Synthesis problem: from the high-voltage line to the distribution board of a villa solved
- Oscillogram of a sinusoidal alternating voltage solved
- Energy balance, electricity meter and fuse rating solved
- Study of a step-down transformer solved
- Transmitting electric power and reducing Joule-effect losses solved
The course of the chapter · All the exercises of the chapter