Physics (Grade 11, Lebanon) · Chapter 15 · Direct application of the course
Energy balance, electricity meter and fuse rating
Alternating current, transformer and household safety · level 2
Statement
In a kitchen supplied at the effective mains voltage , the following three appliances are operated simultaneously for a time (that is, ):
- an electric oven of power ;
- a dishwasher of power ;
- a refrigerator of power .
- How are these three appliances connected to the household installation? Calculate the effective current , , drawn by each appliance, as well as the total current in the line supplying the kitchen.
- Fuses rated , , and are available. What minimum rating must be chosen to protect this line without the fuse blowing during simultaneous operation? What would happen if a fuse were used?
- Calculate the total electrical energy consumed in by these three appliances, in kilowatt-hours (), then in joules ().
Solution
- The three appliances are connected in parallel at the voltage . From , we obtain the effective currents:
The total effective current in the main line is:
- The fuse rating must be the one immediately above the maximum normal current : the fuse must therefore be chosen. With a fuse, since , there would be an overload and the fuse would blow to cut the circuit.
- The total power of the three appliances is . During the time , the total energy consumed is:
In joules ():
Similar exercises
- Synthesis problem: from the high-voltage line to the distribution board of a villa solved
- Oscillogram of a sinusoidal alternating voltage solved
- Study of a step-down transformer solved
- Transmitting electric power and reducing Joule-effect losses solved
- Analyzing an insulation fault and the role of the ground and of the residual current device solved
The course of the chapter · All the exercises of the chapter