Safety diagnosis of a household installation diagram

Alternating current, transformer and household safety · C. Household electrical safety and synthesis problem · level 2

Statement

While renovating an old apartment, an electrician inspects the wiring of a ceiling lamp controlled by a wall switch and that of an electric water heater with a metal tank. He finds three serious faults:

  • Fault A: the switch of the ceiling lamp is placed on the neutral wire (blue), while the phase wire (red) goes directly to the lamp holder without passing through the switch.
  • Fault B: the fuse of the water heater circuit ( at ), rated , has been replaced by a thick twisted iron wire (which melts only above ) because the fuse had blown during a storm.
  • Fault C: the ground terminal (green-yellow) of the metal tank of the water heater is not connected to anything, and the distribution board has no residual current device.

1) Explain why fault A does allow the lamp to be switched on and off, but exposes anyone who changes the bulb while the switch is open (“off”) to a fatal danger.

2) Explain what major danger fault B creates for the apartment if a short circuit or an overload occurs in the water heater.

3) Explain what danger fault C creates for a person taking a shower if the insulation of the heating element cracks and brings the phase wire into contact with the water and the metal tank of the water heater. How does correcting fault C remove this risk?

4) Limiting case. Why is it strictly forbidden to install a socket or to use a mains-powered hair dryer right next to a bathtub full of water, even when the electrical installation of the apartment fully complies with the standards?

Solution

The strategy. For each fault, we determine the potential relative to the ground ( or ) of the accessible parts or the current in the event of a fault, then deduce the physical consequence (electric shock to a person or Joule heating inside the walls).

1) Danger of fault A (switch on the neutral). When the switch placed on the neutral is open, the circuit is open, so the current is zero () and the lamp is indeed off. But since the phase wire () remains directly connected to the lamp socket, the base of the lamp remains live at relative to the ground even when the light is off! A person standing on a stepladder who touches the socket while changing the bulb closes the circuit between the phase () and the ground () and risks electrocution. A switch (like a fuse) must always be placed on the phase.

2) Danger of fault B (fuse replaced by an iron wire). The copper wires embedded in the walls to supply the water heater are designed to carry at most to . In the event of a short circuit or an overload, if the makeshift “fuse” melts only at , a current of or can flow for a long time in the wires inside the walls: the power dissipated by the Joule effect () is multiplied by or , melts the plastic insulating sheaths and starts an electrical fire.

3) Danger of fault C (no ground and no residual current device) and remedy. If the phase touches the metal tank or the water when there is no ground connection, the tank and the water in the pipes are raised to without any current flowing as long as nobody touches them. As soon as a wet person (whose body resistance has fallen to about ) touches the tap or the shower water, a current flows through them and they are electrocuted. By connecting the tank to the ground connection and installing a residual current device, the leakage current escapes immediately through the ground wire as soon as the fault appears and the residual current device cuts off the supply within a few milliseconds.

4) Limiting case: hair dryer in a bathtub. If an appliance connected at falls into the water of a bathtub with a person in it, the soapy water surrounds the whole body (huge contact area, resistance reduced to a few hundred ohms) and the current passes directly from the phase to the neutral or to the pipes through the chest: even a brief flow of current during the to of the mechanical tripping time of a residual current device can be enough to cause cardiac fibrillation.

What the exercise establishes: The three golden rules of household wiring: (1) switches and fuses always on the phase; (2) fuse rating suited to the cross-section of the wires; (3) all metal frames connected to the ground downstream of a residual current device.