Physics (Grade 11, Lebanon) · Chapter 15 · Tutorial exercise

Step-up transformer, step-down transformer and efficiency

Alternating current, transformer and household safety · B. Transformers and transmission of electrical energy at extra-high voltage · level 2

Statement

Two transformers used at the two ends of an energy chain are studied:

  • Transformer (at the output of a power station): its primary winding has turns and receives an effective alternating voltage . Its secondary winding has turns.
  • Transformer (workshop electric welder): connected at its primary ( turns) to the mains , it has at its secondary a winding of very thick copper wire with only turns, so as to melt a welding rod by delivering a very large secondary current .

1) For transformer , calculate the transformation ratio and the effective voltage obtained at the secondary, and state its role. If transmits an ideal power , calculate the effective currents at the primary and at the secondary.

2) For transformer of the electric welder:

  • a) Calculate the transformation ratio and the effective voltage delivered at the secondary. Why is there no danger of electrocution at the secondary of this transformer even though it melts metal?
  • b) Calculate the useful power at the secondary and the current at the primary if were ideal.
  • c) In reality, the efficiency of is . Calculate the real power consumed from the mains as well as the real current drawn at the primary.

3) Limiting case. Why must the secondary winding of the welding transformer ( turns) be made with a very thick copper bar, whereas its primary ( turns) uses a much thinner wire?

Solution

The strategy. We systematically apply (which remains valid with excellent accuracy even for a real transformer), then and .

1) Study of transformer of the power station. The transformation ratio is: Since , is a step-up transformer (which steps the current down). For a transmitted power :

2) Study of transformer of the welder.

  • a) The transformation ratio and the secondary voltage are: The secondary voltage () is six times lower than the safety limit voltage (): it is completely harmless for the operator. It is the enormous current that melts the metal by the Joule effect ().
  • b) The useful power at the secondary is: If were ideal (), the primary current would be (or ).
  • c) With a real efficiency , the power absorbed from the mains and the real primary current are:

3) Limiting case: cross-section of the copper wires. The secondary winding carries a current fifty times larger than the primary ( compared with ). So as not to melt by the Joule effect (), the winding carrying the larger current (the low-voltage one) must always have a much larger copper cross-section (and therefore a much lower resistance ).

What the exercise establishes: Every step-down transformer () also steps the current up (); the low-voltage winding is always the one with the fewest turns but the thickest wire.

Similar exercises