Physics (Grade 11, Lebanon) · Chapter 15 · Tutorial exercise
Step-up transformer, step-down transformer and efficiency
Alternating current, transformer and household safety · B. Transformers and transmission of electrical energy at extra-high voltage · level 2
Statement
Two transformers used at the two ends of an energy chain are studied:
- Transformer (at the output of a power station): its primary winding has turns and receives an effective alternating voltage . Its secondary winding has turns.
- Transformer (workshop electric welder): connected at its primary ( turns) to the mains , it has at its secondary a winding of very thick copper wire with only turns, so as to melt a welding rod by delivering a very large secondary current .
1) For transformer , calculate the transformation ratio and the effective voltage obtained at the secondary, and state its role. If transmits an ideal power , calculate the effective currents at the primary and at the secondary.
2) For transformer of the electric welder:
- a) Calculate the transformation ratio and the effective voltage delivered at the secondary. Why is there no danger of electrocution at the secondary of this transformer even though it melts metal?
- b) Calculate the useful power at the secondary and the current at the primary if were ideal.
- c) In reality, the efficiency of is . Calculate the real power consumed from the mains as well as the real current drawn at the primary.
3) Limiting case. Why must the secondary winding of the welding transformer ( turns) be made with a very thick copper bar, whereas its primary ( turns) uses a much thinner wire?
Solution
The strategy. We systematically apply (which remains valid with excellent accuracy even for a real transformer), then and .
1) Study of transformer of the power station. The transformation ratio is: Since , is a step-up transformer (which steps the current down). For a transmitted power :
2) Study of transformer of the welder.
- a) The transformation ratio and the secondary voltage are: The secondary voltage () is six times lower than the safety limit voltage (): it is completely harmless for the operator. It is the enormous current that melts the metal by the Joule effect ().
- b) The useful power at the secondary is: If were ideal (), the primary current would be (or ).
- c) With a real efficiency , the power absorbed from the mains and the real primary current are:
3) Limiting case: cross-section of the copper wires. The secondary winding carries a current fifty times larger than the primary ( compared with ). So as not to melt by the Joule effect (), the winding carrying the larger current (the low-voltage one) must always have a much larger copper cross-section (and therefore a much lower resistance ).
What the exercise establishes: Every step-down transformer () also steps the current up (); the low-voltage winding is always the one with the fewest turns but the thickest wire.
Similar exercises
- Reading an oscillogram and comparing a DC voltage with an alternating voltage solved
- Power balance, energy meter and monthly bill of a Lebanese household solved
- Electricity transmission: why direct transmission at is physically impossible solved
- Safety diagnosis of a household installation diagram solved
- Physiological effects of current: influence of skin moisture and safety voltage solved